CVE-2026-3611 | Teknoloji dünyasından en güncel haberleri ve güvenlikle ilgili gelişmeleri takip edin.

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user modu…
Critical CVSS: 10.0

CVE-2026-3611

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Vendor
-
Product
-
CWE
CWE-306
Yayın Tarihi
2026-03-12 21:16:27
Güncelleme
2026-03-13 20:06:54